Description
Detail
TeSys LG, enclosed DOL starter, 13…18A, 380 V AC coil. range: TeSys – product name: TeSys LG – device short name: LG1D – device application: safety – utilisation category: AC-3 – device composition: circuit-breaker, contactor, switch disconnector – motor power kW: 4 kW at 220/230 V AC 50/60 Hz, 7.5 kW at 400/415 V AC 50/60 Hz, 9 kW at 440 V AC 50/60 Hz – control type: push-button start white I, push-button stop black O, rotary handle emergency stop red.
Specification
Supporting protocol for PROFINET CBA : No
Supporting protocol for TCP/IP : No
Supporting protocol for SUCONET : No
Suitable for emergency stop : Yes
Supporting protocol for PROFIBUS : No
Supporting protocol for MODBUS : No
Supporting protocol for INTERBUS : No
Supporting protocol for other bus systems : No
Supporting protocol for DeviceNet : No
Supporting protocol for Data-Highway : No
External reset possible : No
Rail mounting possible : No
Supporting protocol for AS-Interface Safety at Work : No
Supporting protocol for LON : No
Supporting protocol for DeviceNet Safety : No
Supporting protocol for EtherNet/IP : No
Supporting protocol for Foundation Fieldbus : No
Supporting protocol for SERCOS : No
With short-circuit release : Yes
Supporting protocol for INTERBUS-Safety : No
Supporting protocol for PROFINET IO : No
Supporting protocol for PROFIsafe : No
Supporting protocol for SafetyBUS p : No
Temperature compensated overload protection : Yes
With fuse : No
Rated operation current at AC-3, 400 V : 18 A
Degree of protection (IP) : IP55
Release class : CLASS 10
Type of electrical connection for auxiliary- and control current circuit : Screw connection
Number of auxiliary contacts as normally open contact : 0
Kind of motor starter : Direct starter
Voltage type for actuating : AC
Number of indicator lights : 0
Height : 165 mm
Width : 175 mm
Rated operation current Ie : 18 A
Depth : 165 mm
Type of electrical connection of main circuit : Screw connection
Ambient temperature, upper operating limit : 40 °C
Number of command positions : 2
Rated operation power at AC-3, 400 V : 7.5 kW
Number of auxiliary contacts as normally closed contact : 0
Rated operation power at AC-3, 230 V, 3-phase : 4 kW
Rated control supply voltage Us at AC 60HZ : 380 – 380 V
Rated control supply voltage Us at AC 50HZ : 380 – 380 V
Overload release current setting : 13 – 18 A
With transformer : No
Supporting protocol for ASI : No
Supporting protocol for CAN : No