Description
Detail
Standard control unit LUCA, class 10, 1,25…5A, 48…72 V DC/AC. range: TeSys – product name: TeSys U – device short name: LUCA – product specific application: basic protection requirements for motor starters: overload and short-circuit – product compatibility: LUFC00, LUFN.. – utilisation category: AC-41, AC-43, AC-44 – motor power kW: 1.5 kW at 400…440 V AC 50/60 Hz, 2.2 kW at 500 V AC 50/60 Hz, 3 kW at 690 V AC 50/60 Hz – [Uc] control circuit voltage: 48 V AC, 48…72 V DC – thermal overload class: class 10 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to IEC 60947-6-2, class 10 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to UL 508, class 20 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to IEC 60947-6-2, class 20 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to UL 508.
Specification
Supporting protocol for Foundation Fieldbus : No
Supporting protocol for Data-Highway : No
Suitable for emergency stop : No
Supporting protocol for SERCOS : No
External reset possible : No
Supporting protocol for DeviceNet : Yes
Supporting protocol for LON : No
Supporting protocol for SUCONET : No
With short-circuit release : Yes
Supporting protocol for other bus systems : Yes
Supporting protocol for EtherNet/IP : No
Supporting protocol for INTERBUS : No
Supporting protocol for INTERBUS-Safety : No
Supporting protocol for DeviceNet Safety : No
Supporting protocol for AS-Interface Safety at Work : No
Rail mounting possible : No
Supporting protocol for PROFINET CBA : No
Supporting protocol for PROFINET IO : No
Supporting protocol for SafetyBUS p : No
With fuse : No
Supporting protocol for PROFIsafe : No
Temperature compensated overload protection : Yes
Number of indicator lights : 0
Release class : CLASS 10
Voltage type for actuating : AC/DC
Number of auxiliary contacts as normally open contact : 0
Number of command positions : 0
Rated operation current Ie : 5 A
Rated operation power at AC-3, 400 V : 1.5 kW
Ambient temperature, upper operating limit : 70 °C
Rated operation current at AC-3, 400 V : 5 A
Number of auxiliary contacts as normally closed contact : 0
Rated control supply voltage Us at AC 50HZ : 48 – 48 V
Degree of protection (IP) : IP20
Overload release current setting : 1.25 – 5 A
Rated control supply voltage Us at AC 60HZ : 48 – 48 V
Rated control supply voltage Us at DC : 48 – 72 V
With transformer : No
Supporting protocol for MODBUS : Yes
Supporting protocol for ASI : Yes
Supporting protocol for PROFIBUS : Yes
Supporting protocol for TCP/IP : No
Supporting protocol for CAN : Yes