Soft starter for asynchronous motor, ATS48, 40A, 208..690 V, 11..37 KW. range of product: Altistart 48 – product or component type: soft starter – product destination: asynchronous motors – product specific application: heavy duty industry and pumps – device short name: ATS48 – motor power kW: 11 kW at 230 V for standard applications, 18.5 kW at 400 V for severe applications, 18.5 kW at 440 V for severe applications, 22 kW at 400 V for standard applications, 22 kW at 440 V for standard applications, 22 kW at 500 V for severe applications, 22 kW at 525 V for severe applications, 30 kW at 500 V for standard applications, 30 kW at 525 V for standard applications, 30 kW at 660 V for severe applications, 30 kW at 690 V for severe applications, 37 kW at 660 V for standard applications, 37 kW at 690 V for standard applications, 9 kW at 230 V for severe applications – motor power hp: 10 hp at 208 V for severe applications, 15 hp at 230 V for standard applications, 25 hp at 460 V for severe applications, 30 hp at 460 V for standard applications, 30 hp at 575 V for severe applications, 40 hp at 575 V for standard applications – power dissipation in W: for standard applications 116 W, for standard applications 142 W – utilisation category: AC-53A – type of start: start with torque control (current limited to 5 In) – IcL starter rating: 47 A (connection in the motor supply line) for severe applications, 47 A (connection in the motor supply line) for standard applications.

Specification

  • Degree of protection (IP) : IP20
  • Voltage type for actuating : AC
  • Rated surrounding temperature without derating : 40 °C
  • Rated power three-phase motor, inline, at 400 V : 22 kW
  • Rated power three-phase motor, inline, at 230 V : 11 kW
  • Rated operation current Ie at 40 °C Tu : 47 A
  • Rated power three-phase motor, inside delta, at 400 V : 0 kW
  • Rated control supply voltage Us at AC 50HZ : 110 – 230 V
  • Rated power three-phase motor, inside delta, at 230 V : 0 kW
  • Rated control supply voltage Us at AC 60HZ : 110 – 230 V
  • Rated control supply voltage Us at DC : 0 – 0 V
  • Rated operating voltage Ue : 208 – 690 V
  • With display : No
  • Internal bypass : No
  • Integrated motor overload protection : Yes
  • Torque control : Yes