Description
Detail
DS951 UL 1P+N RCBO Is A Device That In Two Modules Width Is Able To. Provide Complete Protection Against Overcurrent (Overload And Shortcircuit) And Earth Fault. DS951 UL Are Approved According To UL 1053 Standard Ground-Fault Sensing And Relaying Equipment Making Them Suitable For Installation In Equipments/ Machines Addressed To North American Market.
- · Residual Current Circuit Breaker with Overcurrent
Specification
Rated impulse withstand voltage Uimp : 4 kV
Anti-nuisance tripping version : No
With interlocking device : No
Concurrently switching N-neutral : Yes
Connectable conductor cross section solid-core : 16 – 16 mm²
Connectable conductor cross section multi-wired : 1 – 16 mm²
Ambient temperature during operating : -25 – 55 °C
Current limiting class : 3
Number of protected poles : 1
Width in number of modular spacings : 2
Rated fault current : 0.03 A
Rated insulation voltage Ui : 500 V
Rated voltage : 230 V
Rated short-circuit breaking capacity IEC 60947-2 : 6 kA
Release characteristic : B
Number of poles (total) : 2
Over voltage category : 3
Rated current : 10 A
Built-in depth : 70 mm
Pollution degree : 2
Rated short-circuit breaking capacity acc. EN 61009 : 6 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1 : 6 kA
Disconnection characteristic : Undelayed
Surge current capacity : 0.25 kA
Leakage current type : AC
Degree of protection (IP) : IP20
Voltage type : AC
Frequency : 50/60 Hz