PM5563 powermeter w 1mod2eth, upto 63th H, 1,1M 4DI/2DO 52alarms, DIN

£1,903.75 inc VAT £1,586.46 ex VAT

Description

PM5560 no display 4DI/2DO Modbus & Ether

  • · This device is a DIN-mount energy meter without display.
  • · The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle.
  • · The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic.
  • · Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration.
  • · This meter also feature the direct monitoring of neutral current.
  • · The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC.
  • · Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations.
  • · The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz.
  • · Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz.
  • · Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support.