MPCB Gv2P Triple Pole 1-1.6A 100Ka Thermal Magnetic Rotary Knob

£112.32 inc VAT £93.60 ex VAT

SKU: 2500053523 Category: Tag:

Description

Detail

Schneider circuit breaker using thermal-magnetic trip unit technology applicable for motors.

  • · TeSys GV motor circuit breaker, 3 poles (3P), 1.6A/690V, for 3-phase motor applications 0.37-0.55kW@400V.
  • · It provides a thermal-magnetic protection with a thermal setting range 1-1.6A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V.
  • · Connection by screw clamp terminals.
  • · Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3.
  • · Fixing mode: Clipped on 35mm symmetrical DIN rail
  • · Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
  • · Tightening torque: 1.7Nm on screw terminals
  • · Mechanical/Electrical durability: 100000 cycles
  • · Ambient temperature: -20°C to 60°C
  • · IP20/IK04 Degree of protection

Specification

  • Width : 45 mm
  • Phase failure sensitive : Yes
  • With integrated under voltage release : No
  • With integrated auxiliary switch : No
  • Thermal protection : Yes
  • Adjustment range undelayed short-circuit release : 0 – 0 A
  • Rated operating voltage : 690 – 690 V
  • Overload release current setting : 1 – 1.6 A
  • Height : 89 mm
  • Height : 89 mm
  • Number of poles : 3
  • Degree of protection (IP) : IP20
  • Rated operation power at AC-3, 400 V : 0.55 kW
  • Rated operation power at AC-3, 230 V : 0 kW
  • Rated permanent current Iu : 1.6 A
  • Depth : 97 mm
  • Depth : 97 mm
  • Rated short-circuit breaking capacity lcu at 400 V, AC : 100 kA
  • Type of electrical connection of main circuit : Screw connection
  • Width : 45 mm
  • Device construction : Complete device in housing
  • Switch off technique : Thermomagnetic