Description
Detail
Molded case circuit breaker 3RV1 for motor protection Standard switching capacity Rated current In = 100 A electronic release Short-circuit protection adjustable 6-13 x In Overload protection adjustable 0.4-1 x In, Class 10A-30 Icu = 120 kA at 400 V 3-pole, Screw terminal including phase barriers Simple, efficient and always up to date – SIRIUS modular system.
Specification
Rated operating voltage : 690 – 690 V
Phase failure sensitive : Yes
With thermal protection : No
With integrated under voltage release : No
With integrated auxiliary switch : No
Height : 205 mm
Adjustment range undelayed short-circuit release : 1300 – 1300 A
Thermal protection : No
Overload release current setting : 40 – 100 A
Depth : 103.5 mm
Degree of protection (IP) : IP20
Width : 105 mm
Rated operation power at AC-3, 230 V : – kW
Rated operation power at AC-3, 400 V : 55 kW
Rated short-circuit breaking capacity lcu at 400 V, AC : 120 kA
Rated permanent current Iu : 250 A
Number of poles : 3
Device construction : Built-in device fixed built-in technique
Type of control element : Rocker lever