Description
Detail
Miniature circuit breaker 400 V 6kA, 4-pole, B, 16A, D=70 mm
Specification
Rated short-circuit breaking capacity Icn EN 60898 at 230 V : 6 kA
Concurrently switching N-neutral : No
Additional equipment possible : Yes
Suitable for flush-mounted installation : No
Ambient temperature during operating : -25 – 55 °C
Connectable conductor cross section multi-wired : 0.75 – 35.0 mm²
Connectable conductor cross section solid-core : 0.75 – 35.0 mm²
Frequency : 50 – 50 Hz
Rated insulation voltage Ui : 440 V
Rated voltage : 400 V
Built-in depth : 70 mm
Rated impulse withstand voltage Uimp : 4 kV
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V : 15 kA
Degree of protection (IP) : IP20
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V : 15 kA
Rated short-circuit breaking capacity Icn EN 60898 at 400 V : 6 kA
Rated current : 16 A
Number of protected poles : –
Pollution degree : 3
Width in number of modular spacings : 4
Number of poles (total) : 4
Over voltage category : 3
Current limiting class : 3
Voltage type : AC
Release characteristic : B