Description
Detail
Miniature circuit breaker 230/400 V 10kA, 1-pole, B, 6A
- · CIRCUIT BREAKER 10KA 1POLE B6
Specification
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V : 10 kA
Additional equipment possible : Yes
Concurrently switching N-neutral : No
Suitable for flush-mounted installation : No
Connectable conductor cross section solid-core : 0.75 – 25.0 mm²
Connectable conductor cross section multi-wired : 0.75 – 25.0 mm²
Ambient temperature during operating : -25 – 55 °C
Built-in depth : 70 mm
Frequency : 50 – 50 Hz
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V : 10 kA
Rated voltage : 400 V
Degree of protection (IP) : IP20
Rated short-circuit breaking capacity Icn EN 60898 at 230 V : 10 kA
Rated short-circuit breaking capacity Icn EN 60898 at 400 V : 10 kA
Current limiting class : 3
Rated current : 6 A
Number of poles (total) : 1
Width in number of modular spacings : 1
Pollution degree : 2
Over voltage category : 3
Release characteristic : B
Voltage type : AC