MCCB Compact Triple Pole 3D 250A 36Ka Micrologic 2.2 Electro

£1,115.71 inc VAT £929.76 ex VAT

Description

Detail

250A 3P3d 36kA NSX250F ML 2.2

  • · This Compact NSX250F is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity.
  • · It is an optimal choice for all standard and specific applications.
  • · The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz.
  • · The operational voltage is 690VAC 50/60Hz.
  • · This product embeds an electronic Micrologic 2.2 trip unit, with 250A rating.
  • · Micrologic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection.
  • · This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.
  • · It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.
  • · Compact NSX250F is part of Schneider Electric EcoStruxure Power architecture.

Specification

  • Rated voltage : 0 – 0 V
  • DIN rail (top hat rail) mounting optional : No
  • Complete device with protection unit : Yes
  • With under voltage release : No
  • Motor drive optional : Yes
  • Integrated earth fault protection : No
  • Suitable for DIN rail (top hat rail) mounting : No
  • With switched-off indicator : No
  • Motor drive integrated : No
  • Adjustment range undelayed short-circuit release : 3000 – 3000 A
  • Adjustment range short-term delayed short-circuit release : 135 – 2500 A
  • Overload release current setting : 225 – 250 A
  • Degree of protection (IP) : IP30
  • Number of auxiliary contacts as change-over contact : 0
  • Number of auxiliary contacts as normally open contact : 0
  • Number of poles : 3
  • Rated permanent current Iu : 250 A
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 36 kA
  • Number of auxiliary contacts as normally closed contact : 0
  • Device construction : Built-in device fixed built-in technique
  • Type of control element : Rocker lever
  • Type of electrical connection of main circuit : Screw connection
  • Position of connection for main current circuit : Front side