MCCB Compact Four Pole 4D 250A 36Ka Tm-D Thermal Magnetic

£2,064.47 inc VAT £1,720.39 ex VAT

Description

Detail

250A 4P4d 36kA NSX250F TM-D

  • · This Compact NSX250F is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity.
  • · It is an optimal choice for all standard and specific applications.
  • · The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz.
  • · The operational voltage is 690VAC 50/60Hz.
  • · This product embeds a 250A rating thermal-magnetic trip unit (TMD).
  • · TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
  • · This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories.
  • · It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.
  • · Compact NSX250F is part of Schneider Electric EcoStruxure Power architecture.

Specification

  • Rated voltage : 0 – 0 V
  • DIN rail (top hat rail) mounting optional : No
  • Complete device with protection unit : Yes
  • With under voltage release : No
  • Motor drive optional : Yes
  • Integrated earth fault protection : No
  • Suitable for DIN rail (top hat rail) mounting : No
  • Motor drive integrated : No
  • With switched-off indicator : No
  • Adjustment range short-term delayed short-circuit release : 0 – 0 A
  • Adjustment range undelayed short-circuit release : 1250 – 2500 A
  • Overload release current setting : 175 – 250 A
  • Degree of protection (IP) : IP30
  • Number of auxiliary contacts as normally open contact : 0
  • Rated permanent current Iu : 250 A
  • Number of auxiliary contacts as change-over contact : 0
  • Number of poles : 4
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 36 kA
  • Number of auxiliary contacts as normally closed contact : 0
  • Type of control element : Rocker lever
  • Device construction : Built-in device fixed built-in technique
  • Type of electrical connection of main circuit : Screw connection
  • Position of connection for main current circuit : Front side