E3H800Pr122/P-Lsigin=800A3Pfh

£14,698.97 inc VAT £12,249.14 ex VAT

Description

Detail

SACE EMAX CIRCUIT-BREAKER E3H 800A THRE-POLE FIXED WITH TERMINALS REAR HORIZONTAL OVERCURRENT RELEASE PR122/P-LSIG R800 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

  • · Air Circuit Breaker

Specification

  • Rated voltage : 690 – 690 V
  • Complete device with protection unit : Yes
  • DIN rail (top hat rail) mounting optional : No
  • Motor drive optional : Yes
  • Integrated earth fault protection : Yes
  • Suitable for DIN rail (top hat rail) mounting : No
  • With switched-off indicator : Yes
  • Motor drive integrated : No
  • Adjustment range short-term delayed short-circuit release : 480 – 480 A
  • Adjustment range undelayed short-circuit release : 1200 – 12000 A
  • Overload release current setting : 320 – 800 A
  • Degree of protection (IP) : IP30
  • Number of auxiliary contacts as normally open contact : 0
  • Number of auxiliary contacts as change-over contact : 4
  • Number of poles : 3
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 100 kA
  • Rated permanent current Iu : 800 A
  • Number of auxiliary contacts as normally closed contact : 0
  • Device construction : Built-in device fixed built-in technique
  • Type of control element : Push button
  • Type of electrical connection of main circuit : Bolt connection
  • Position of connection for main current circuit : Back side