Description
Detail
Schneider Electric ATV212WU75N4 Altivar 212 7.5kW variable speed drive for pumps and fans in HV AC incorporates flux vector control without sensor, standard asynchronous motor control profile. APOGEE FLN, BACnet, LonWorks, METASYS N2 and Modbus communication port protocol. 40 to 50°C with derating factor operating temperature. Conforms to 3 IEC 61800-5-1 pollution degree.
- · Current Rating: 16A
- · Height: 340mm
- · Range: Altivar 212
- · Width: 230mm
- · Weight: 10.95kg
- · For Use With Motor: ATV212 Asynchronous
- · Depth: 208mm
- · IP Rating: IP55
- · Supply Voltage: 380 to 480V
Specification
Supporting protocol for DeviceNet Safety : No
Supporting protocol for INTERBUS : No
Supporting protocol for TCP/IP : No
Supporting protocol for ASI : No
Supporting protocol for PROFIBUS : No
Supporting protocol for MODBUS : Yes
Supporting protocol for other bus systems : Yes
Supporting protocol for Data-Highway : No
Supporting protocol for INTERBUS-Safety : No
Supporting protocol for LON : Yes
Supporting protocol for SERCOS : No
Supporting protocol for DeviceNet : No
Supporting protocol for SUCONET : No
With control unit : Yes
Supporting protocol for CAN : No
Supporting protocol for AS-Interface Safety at Work : No
Supporting protocol for EtherNet/IP : No
Supporting protocol for Foundation Fieldbus : No
With PC connection : Yes
Application in industrial area permitted : Yes
Supporting protocol for PROFINET IO : No
Supporting protocol for SafetyBUS p : No
Supporting protocol for PROFINET CBA : No
Supporting protocol for PROFIsafe : No
4-quadrant operation possible : No
Integrated breaking resistance : No
Application in domestic- and commercial area permitted : Yes
Max. output at quadratic load at rated output voltage : 0 kW
Degree of protection (IP) : IP55
Mains frequency : 50/60 Hz
Number of phases input : 3
Number of interfaces PROFINET : 0
Type of converter : I converter
Number of HW-interfaces parallel : 0
Number of HW-interfaces RS-232 : 0
Number of HW-interfaces serial TTY : 0
Number of HW-interfaces RS-485 : 1
Relative symmetric net voltage tolerance : 0 %
Number of HW-interfaces RS-422 : 0
Number of HW-interfaces industrial Ethernet : 0
Number of HW-interfaces USB : 0
Number of phases output : 3
Number of HW-interfaces other : 0
Width : 230 mm
Height : 340 mm
Nominal output current I2N : 16 A
Depth : 208 mm
Max. output voltage : 480 V
Relative symmetric net frequency tolerance : 5 %
Max. output frequency : 200 Hz
Max. output at linear load at rated output voltage : 7.5 kW
Mains voltage : 380 – 480 V
With optical interface : No
Supporting protocol for KNX : No