Advanced control unit LUCD, class 20, 8…32A, 110…220 V DC/AC

£292.51 inc VAT £243.76 ex VAT

SKU: 2500246619 Category: Tag:

Description

Advanced control unit LUCD, class 20, 8…32A, 110…220 V DC/AC. range: TeSys – product name: TeSys U – device short name: LUCD – product specific application: basic protection and advanced functions, communication – product compatibility: LUFC00, LUFDA01, LUFDA10, LUFDH11, LUFN.., LUFV2, LUFW10 – utilisation category: AC-41, AC-43, AC-44 – motor power kW: 15 kW at 400…440 V AC 50/60 Hz, 15 kW at 500 V AC 50/60 Hz, 18.5 kW at 690 V AC 50/60 Hz – [Uc] control circuit voltage: 110…220 V DC, 110…240 V AC – thermal overload class: class 20 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to IEC 60947-6-2, class 20 – frequency limit: 40…60 Hz – temperature compensation: -25…70 °C – conforming to UL 508.

  • · TeSys U control and diagnostic unit to be inserted in advanced power bases LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 15kW@400V.
  • · It provides full protection to motors with a rated current Ir 8-32A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only).
  • · It provides a thermal overload alarm to be used locally using a LUFDA module or remotely using a LULC module, and a test push button for overload simulation.
  • · To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base).