Detail
MOVING PART FOR C.BREAKER SACE EMAX2 E4.2N 4000 FOUR-POLE WITH SOLID-STATE RELEASE IN AC EKIP/G/HI-TOUCH-LSIG R 4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specification
Number of auxiliary contacts as normally open contact : 0
Complete device with protection unit : Yes
Motor drive optional : Yes
DIN rail (top hat rail) mounting optional : No
Integrated earth fault protection : Yes
Suitable for DIN rail (top hat rail) mounting : No
Motor drive integrated : No
With switched-off indicator : Yes
Adjustment range short-term delayed short-circuit release : 2400 – 40000 A
Adjustment range undelayed short-circuit release : 6000 – 60000 A
Overload release current setting : 1600 – 4000 A
Degree of protection (IP) : IP30
Rated voltage : 690 – 690 V
Number of poles : 4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 66 kA
Number of auxiliary contacts as change-over contact : 4
Device construction : Built-in device slide-in technique (withdrawable)
Rated permanent current Iu : 4000 A
Number of auxiliary contacts as normally closed contact : 0
Type of control element : Push button
Type of electrical connection of main circuit : Connection at separate chassis part
Position of connection for main current circuit : Connection at separate chassis part