Description
Detail
The DS202C Series RCBO Is A 2P In Two-Modules Device For The Protection Of End User Single-Phase Circuits Against Overload And Short-Circuit Currents. Provides An Optimal Trade-Off Between Safety And Continuity Of Service, Thanks To The Resistance To Unwanted Trippings. Protection Against Indirect Contacts And Additional Protection Against Direct Contacts (With Sensitivity = 30 MA). Protection And Isolation Of Resistive And Inductive Loads.
- · Residual Current Circuit Breaker with Overcurrent
Specification
Rated short-circuit breaking capacity IEC 60947-2 : 10 kA
Anti-nuisance tripping version : Yes
With interlocking device : Yes
Concurrently switching N-neutral : Yes
Connectable conductor cross section solid-core : 25 – 25 mm²
Connectable conductor cross section multi-wired : 1 – 25 mm²
Ambient temperature during operating : -25 – 55 °C
Number of protected poles : 2
Current limiting class : 3
Width in number of modular spacings : 2
Rated fault current : 0.3 A
Rated insulation voltage Ui : 500 V
Rated voltage : 230 V
Rated impulse withstand voltage Uimp : 4 kV
Voltage type : AC
Number of poles (total) : 2
Over voltage category : 3
Rated current : 32 A
Built-in depth : 69 mm
Rated short-circuit breaking capacity acc. EN 61009 : 10 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1 : 10 kA
Degree of protection (IP) : IP2X
Pollution degree : 2
Surge current capacity : 3 kA
Disconnection characteristic : Short-time delayed
Frequency : 50/60 Hz
Leakage current type : A
Release characteristic : B