E2B1000Pr123/Dcin=1000A4Pfvr<

£20,894.45 inc VAT £17,412.04 ex VAT

Description

Detail

SACE EMAX CIRCUIT-BREAKER E2B 1000A FOUR-POLE FIXED WITH TERMINALS REAR VERTICAL OVERCURRENT RELEASE PR123/DC R1000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

  • · Air Circuit Breaker

Specification

  • Rated voltage : 1000 – 1000 V
  • Complete device with protection unit : Yes
  • DIN rail (top hat rail) mounting optional : No
  • Motor drive optional : Yes
  • Integrated earth fault protection : No
  • Suitable for DIN rail (top hat rail) mounting : No
  • With switched-off indicator : Yes
  • Motor drive integrated : No
  • Adjustment range short-term delayed short-circuit release : – – – A
  • Adjustment range undelayed short-circuit release : 1500 – 15000 A
  • Overload release current setting : 400 – 1000 A
  • Degree of protection (IP) : IP30
  • Number of auxiliary contacts as normally open contact : 0
  • Number of auxiliary contacts as change-over contact : 4
  • Number of poles : 4
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : – kA
  • Rated permanent current Iu : 1000 A
  • Number of auxiliary contacts as normally closed contact : 0
  • Device construction : Built-in device fixed built-in technique
  • Type of control element : Push button
  • Type of electrical connection of main circuit : Bolt connection
  • Position of connection for main current circuit : Back side