SACE EMAX CIRCUIT-BREAKER E4S 4000A/F FULL SIZE NEUTRAL FOUR-POLE FIXED WITH TERMINALS REAR HORIZONTAL OVERCURRENT RELEASE PR122-LSIG R4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
Specification
Adjustment range undelayed short-circuit release : 6000 – 60000 A
Complete device with protection unit : Yes
DIN rail (top hat rail) mounting optional : No
Motor drive optional : Yes
Integrated earth fault protection : Yes
Suitable for DIN rail (top hat rail) mounting : No
With switched-off indicator : Yes
Motor drive integrated : No
Overload release current setting : 1600 – 4000 A
Adjustment range short-term delayed short-circuit release : 2400 – 2400 A
Rated voltage : 690 – 690 V
Position of connection for main current circuit : Back side
Number of auxiliary contacts as normally open contact : 0
Number of auxiliary contacts as change-over contact : 4
Number of poles : 4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 80 kA
Rated permanent current Iu : 4000 A
Device construction : Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact : 0
Type of control element : Push button
Type of electrical connection of main circuit : Bolt connection
Degree of protection (IP) : IP30