3LD Switch Disconnector, Main Switch, 3-Pole, Iu: 125 A, Operating Power/…

£159.70 inc VAT £133.08 ex VAT

Description

Detail

SENTRON, Switch disconnector 3LD, main switch, 3-pole, Iu: 125 A, Operating power / at AC-23 A at 400 V: 45 kW, installation in distribution boards, knob-operated mechanism, black, handle direct at the switch The 3LD main and emergency off switch for safe disconnection of loads in a wide variety of environments. There are numerous possible applications for the 3LD3 disconnector units. After disconnects from the grid, they ensure safe activation of all of the electrical equipment, thus switch, for example, to three-phase motors, but also air-conditioning and ventilation systems. 3LD3 are also ideal for control panels, in particular for applications in small machines (for example saws, compressors, pumps, concrete mixers, drills, mills, and woodworking machinery) Key features of the Siemens 3LD main and emergency off switches: 1. Modular design, fast and easy mounting of auxiliary switches, N-PE terminal, or 4-pole 2. Versatile thanks to local approvals. 3. One mechanical size for five electrical sizes. 4. Can be used for DC applications. 5. Types of mounting: Front mounting, mounting plate, standard mounting rail. 6. Optimized disconnect from 16 A to 63 A with lockable rotary operating mechanism.

Specification

  • Version as reversing switch : No
  • Rated operating voltage : – V
  • Suitable for ground mounting : Yes
  • Suitable for front mounting centre : No
  • Suitable for front mounting 4-hole : No
  • Switching power at 400 V : – kW
  • Suitable for distribution board installation : No
  • Suitable for intermediate mounting : No
  • Motor drive optional : No
  • Max. rated operation voltage Ue AC : 690 V
  • Voltage release optional : No
  • Interlockable : Yes
  • Motor drive integrated : No
  • Version as main switch : Yes
  • Version as safety switch : Yes
  • Version as maintenance-/service switch : Yes
  • Version as emergency stop installation : No
  • Number of poles : 3
  • Type of electrical connection of main circuit : Frame clamp
  • Type of control element : Toggle
  • Degree of protection (IP), front side : IP40
  • Device construction : Built-in device fixed built-in technique
  • Number of auxiliary contacts as change-over contact : 0
  • Number of auxiliary contacts as normally open contact : 0
  • Number of switches : 1
  • Number of auxiliary contacts as normally closed contact : 0
  • Colour control element : Black
  • Rated permanent current at AC-21, 400 V : 125 A
  • Rated permanent current at AC-23, 400 V : 80 A
  • Rated permanent current Iu : 125 A
  • Rated short-time withstand current lcw : 2 kA
  • Conditioned rated short-circuit current Iq : – kA
  • Rated operation power at AC-3, 400 V : 37 kW
  • Rated operation power at AC-23, 400 V : 45 kW