Detail

The Circuit Breaker For Transformer Protection MS132-16T Is A Compact 45 Mm Width Device Designed To Protect Control Transformers On The Primary Side. This Device Has A Rated Operational Current Of Ie = 16 A. It Allows Fuse-Less Protection Against Overload And Short-Circuit. The Short-Circuit Current Setting Is Fixed To 20 Times The Rated Operational Current To Handle The High Inrush Current Generated By Transformers. The Device Allows Manually Connect And Disconnect The Transformer From The Mains Thanks Of Its Built-In Disconnection Function. The Circuit Breaker For Transformer Protection Offers A Rated Service Short-Circuit Breaking Capacity Of Ics = 100 KA At 400 VAC And A Trip Class 10. Further Features Are Temperature Compensation, Trip-Free Mechanism, Rotary Handle With A Clear Switch Position Indication And Short Circuit Trip Indicator. The Handle Is Lockable To Protect Against Unauthorized Changes. Auxiliary Contacts, Signalling Contacts, Undervoltage Releases, Shunt Trips, Power In-Feed Blocks And Terminal Spacers Are Available As Accessory.

  • · Circuit Breaker for Primary Transformer Protection

Specification

  • Rated voltage : 690 – 690 V
  • Complete device with protection unit : Yes
  • DIN rail (top hat rail) mounting optional : Yes
  • Motor drive optional : No
  • Suitable for DIN rail (top hat rail) mounting : Yes
  • Integrated earth fault protection : No
  • With switched-off indicator : Yes
  • Motor drive integrated : No
  • Adjustment range short-term delayed short-circuit release : – – – A
  • Adjustment range undelayed short-circuit release : 320 – 320 A
  • Overload release current setting : 10 – 16 A
  • Degree of protection (IP) : IP20
  • Number of auxiliary contacts as normally open contact : 0
  • Number of auxiliary contacts as change-over contact : 0
  • Number of poles : 3
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz : 100 kA
  • Rated permanent current Iu : 16 A
  • Number of auxiliary contacts as normally closed contact : 0
  • Device construction : Complete device in housing
  • Type of control element : Turn button
  • Position of connection for main current circuit : Front side
  • Type of electrical connection of main circuit : Screw connection